Hot Stuff: Continuous Duty Electric Locking Devices

The Ohm Symbol

I regularly hear complaints about electric strikes, cylindrical locks or mortise locks that are hot to the touch.   When I ask, I am always answered that, yes, the device is being used in a continuous duty application.

Continuous duty means that the electric lock or strike is powered continuously, usually for several hours a day.  Most fail safe locks and strikes are run continuously, since they are usually locked part of the day and they require electric power to lock.  Whenever a door is kept unlocked by using an electrical timer, the lock or strike that is controlled by the time is run continuously for part of the timing cycle.

Heat in an electric lock or strike is caused by resistance in the electrical circuit as it passes through the coil of the solenoid inside the device.  Often this heat is sufficient to “burn out” the solenoid.   The solenoid does not actually catch fire, usually.  The term, “burned out” refers to a solenoid that has been ruined by excessive heat so that it no longer functions.

Heat from electrical resistance is exacerbated when there are problems with the supply of power.  For example, if the power supply provides less than sufficient amperage to constantly power the solenoid, the solenoid will ‘run’ hotter.  Similarly if there is a current drop because of a long wire run with inadequate wire gauge, the solenoid will not get sufficient current and will run hot.  Also if the voltage supplied is significantly higher than the solenoid is rated to accept, that could create a heat problem as well.

Often, however, there is no detectable reason for the solenoid to run hot.  Sometimes, it seems, they just do.

A great way to mitigate the problem of the hot lock or strike (when all power supply problems have been solved) is to use an electrical device in line with the electric lock or strike that provides it with a full inrush voltage and current upon activation and then reduces the voltage and/or current to a holding level, allowing the solenoid to run cooler.

Several companies offer these units.  Here are some examples:

  • HES:  Model 2005M3 Smart Pack controller
  • COMMAND ACCESS:  CRU-2 current reduction unit
  • TRINE:  LC-100 line conditioner

 

 

Full Height Housings for Electromagnetic Locks

Maglocks are generally great problems solvers, but they also create problems.  One significant problem is the fact that they are usually installed on the header, and therefore only lock the top of the door.  If the only lock on the door is a magnetic lock and the door is fairly flexible, a reasonably strong person may be able to pull the bottom of the door open four or more inches.

One solution to this problem is to install mags top and bottom on the lock side leg of the frame rather than on the header.  If you have an opening that measures at least 35 inches from stop to stop and you use magnets that are three inches wide or less, you can install mags in the opening and still have 32 inches clear to comply with the American Disabilities Act.  The problem with this idea is that no matter where they are installed in the opening, users are likely to bump into them with some body part or other.

Enter the full height housing for electromagnetic locks, an enclosure that houses one or two maglocks and mounts on the stop of the lock side leg of the door jamb as illustrated below.

The illustration above is one I prepared for a customer so that I could order a custom built, full height housing for two electromagnetic locks.  The drawing shows the dimensions I requested as indicated by the lines with arrows at both ends:  height of the opening from threshold to header stop; distance from header stop to center line of upper maglock prep; distance from threshold to center line of lower mag prep; and distance between the center lines of the mag preps.

Provided the opening is at least 35 inches clear and the housing is no more than three inches wide, the opening will still comply with ADA after the full height housing system is installed.

 

Multi-function Doorways, Part One

As seen in Doors and Hardware Magazine.

Whenever something is invented, humans find more uses for it.  This is certainly true for door automation and electric locking.  It was not long after people realized a door could be unlocked remotely using an electric strike and a door could be opened automatically using a power operator (automatic door opener) that they began using these devices together.   Of course this combination of devices was soon interfaced with intercoms.  Exit devices with electric latch retraction and electromagnetic locks were thrown into the mix, as well as access control, delayed egress and/or security interlock systems.  Any of these systems alone is sufficient to complicate an installation, but when you start to use several on one opening, that’s when things really start to get interesting.

A hospital can be one of the best places to run into a doorway that needs to perform many functions (pun intended).  Hospitals seem to have more varied reasons to keep different people out at different times, or to let them in or out by different means.  In addition to standard life safety and security issues, hospitals also have to anticipate the needs of patients who may be under the influence of medication and/or mental disorders and/or have physical limitations.  Some patients must be kept inside for their own safety while all patients must be able to exit swiftly and safely in the event of a fire.

Let’s use as an example a hospital emergency ward entrance used primarily by ambulance drivers.  The hospital wants only ambulance personnel and the security guard  to be able to activate the power operator, and to control access by use of a remote switch operated by the security guard  for the general public and an access code by hospital employees (other than ambulance personnel).

Since it is a pair of doors, concealed vertical rod exit devices are the most efficient, safe and secure way to lock them and provide reliable free egress in the event of an emergency.  However, since there is a power operator involved, these devices must be equipped with electric latch retraction; and since use of the power operator was to be limited, a second electric means of opening the door would be required.

A simple way to solve the problem of the second means of unlocking is by using electrified exit device lever trim with one of the concealed vertical rod exit devices.  Persons not requiring the power operator can get in by using the access control, or the security guard  can “buzz” them in using one of two remote buttons.  Because there will be two means of unlocking the door electrically, the security guard  will need a small desk unit with two buttons:  one that activates the power operator and electric latch retraction and one that activates the electric exit device trim.

Below is an amateur wiring diagram (made by me) of how, basically, the system works.

Central to the concept is an access control device with two relays and a request to exit input.  This allows several of the connections to be made through the access control system.  If the access control system on site does not provide more than one relay, the same functions can be accomplished by using additional relays in the power supply.

The system as shown in my illustration above works like this:

Ambulance personnel activate the power operator using the access control system.  The access control system signals the power operator via contact closure in Relay #1.  The power operator triggers the relay in the power supply to retract the latches of the exit devices, then opens the door.

Other authorized hospital personnel use the access control system to unlock the lever trim.  The access control system changes the state of Relay #2, triggering the relay in the power supply to unlock the trim.  They turn the lever, pull the door open and walk in.

Injured people arrive on foot at the Emergency Room entrance.  The Security Guard sees them (or is notified by intercom, not shown) and lets them in by pressing the red button, activating the power operator, or by pressing the green button that unlocks the exit device trim.

There exist many possible variations of this system.  Knowledge of access control systems and door hardware are required, but the most important principal in play is the use of contact closure to signal multiple devices.


The Elusive “Touch Chip” Credential

A few years ago, Ingersoll Rand (IR) purchased Locknetics Security Engineering in Connecticut, and since then gradually rebranded the line as Schlage Electronics.   A little over a year ago, as part of the process of closing the Connecticut facility, Schlage Electronics started phasing out its TR80 and TR81 touch readers.  These readers were based on the old technology of the Dallas chip, otherwise known IR/Locknetics land as the touch chip or iButton.  By the end of 2010, Schlage phased out all commercial electronic locking products that incorporated touch chip readers, such as touch readers and locking technologies that incorporated the touch reader, such as the CM line of computer managed locks and their electromagnetic locks with on-board access control.

When the new price books were released in January 2011, the touch chip credential was completely absent.   When questioned about legacy systems, representatives from IR indicated that touch chip users should migrate over to prox tags.  With the new AD and CO series electronic locks, Schlage made available new software and a new hand held programmer (the HHD-KIT) that is backwards compatible with the old hardware.  They also produced a tag with a prox chip on one side and a touch chip on the other so that legacy facilities would be able to carry both credentials over the period of years during which the old CM or other series locks would age out of the system.

One might think that the touch chip has completely faded from the Schlage Electronics scene, but such is not the case.  Looking through the Multi-Family Price Book what do I discover but the new SRT-100 touch reader and a barrage of “iButton” touch chip credentials such as the one pictured.   The new CT-5000 controller that replaces the old CT-1000 controller is also available for those who need to replace ailing legacy systems.  It is my understanding that the iButtons that appear under the multi-family division are fully compatible with legacy technologies such as CM locks or KC-2 series locks.

There is also a new line of smart residential locks that incorporate touch chip technology.  So it is safe to say that touch chip technology is not going to disappear anytime soon.  So if you have a large facility full of old Locknetics products that take iButtons, don’t panic.  At least for now you can still get them.

 

New PS914RFK Retro-fit Kit from Von Duprin

According to IR tech support, the PS914RFK is a bracket and main board assembly designed to install into existing PS873 enclosures.  The idea is to ease PS873 replacement and it looks to me like it will accomplish that.

In addition to the PS873, you will need to replace all existing option boards that are present.

  • To replace 871-2, use 900-2RS
  • To replace 873-BB, use 900-BBK if you need batteries included.  If not, use 900-BB for the board only
  • To replace 873-FA, use 900-FA
  • To replace 873-4TD, 873-AO, or 873-SI, use 900-4RL
  • To replace 873-2Q, use 900-2Q

The following boards have been discontinued:

  • 873-AL
  • 873-AC
  • 873-DE

In several pieces of Ingersoll Rand literature I have seen the 900-BB board depicted as if it includes batteries.  It does not.  So if you want your battery kit to come with batteries, you need to get the 900-BBK.

 

PS900 Series Schlage Electronics and Von Duprin Power Supplies Demystified

Von Duprin and Schlage Electronics are divisions of Ingersoll Rand. Both are major manufacturers of power supplies for use with electric locking systems and access control. As of January 1st, 2011, Ingersoll Rand discontinued two of their power supply product lines, the PS800 series Von Duprin and the Schlage Electronics 500 series, and merged them into the new PS900 series.

A split in power supply branding may or may not remain, depending on what document you are looking at, but whether they say they are Schlage or Von Duprin, they are all the same PS900 series.

Here is the lineup:

PS902 – 2 Amp output at 12 or 24VDC, field selectable

Compatible with these option boards:

  • 900-BBK: Battery Backup – back up power in case of power outage, includes batteries
  • 900-FA: Fire Alarm – relay for interface with fire alarm panel  – wires to main board
  • 900-2Q: 2 Relay QEL control Board – to run 2 Von Duprin QEL devices
  • 900-4R: 4 Relay Output Board – four relay outputs to operate 4 electric locking devices, not QEL or EL
  • 900-4RL: 4 Relay Logic Board – for man trap or security interlock systems or up to 4 QEL devices
  • 900-8F: Fused 8 Zone Distribution Board – 8 outputs, fused for circuit protection
  • 900-8P: PTC 8 Zone Distribution Board – 8 outputs, circuit breaker protected

PS902 can accommodate 1 of the above option boards in addition to the 900-FA option and battery backup.

For use with electric locks and with Von Duprin Quiet Electric Latch retraction (QEL) exit devices, but NOT with Von Duprin electric latch retraction (EL) exit devices.

PS904 – 4 Amp output at 12 or 24VDC, field selectable

Compatible with these option boards:

  • 900-BBK: Battery Backup – back up power in case of power outage, includes batteries
  • 900-FA: Fire Alarm – relay for interface with fire alarm panel  – wires to main board
  • 900-2Q: 2 Relay QEL control Board – to run 2 Von Duprin QEL devices
  • 900-4R: 4 Relay Output Board – four relay outputs to operate 4 electric locking devices, not QEL or EL
  • 900-4RL: 4 Relay Logic Board – for man trap or security interlock systems
  • 900-8F: Fused 8 Zone Distribution Board – 8 outputs, fused for circuit protection
  • 900-8P: PTC 8 Zone Distribution Board – 8 outputs, circuit breaker protected

PS904 can accommodate up to 2 option boards and battery back up.

Note:  no plug-in for fire alarm relay on main board.  900-FA is only usable with the PS904 if used with an option board.

For use with electric locks and with Von Duprin Quiet Electric Latch retraction (QEL) exit devices, but NOT with Von Duprin electric latch retraction (EL) exit devices.

PS906 – 6 Amp output at 12 or 24VDC, field selectable

Compatible with these option boards:

  • 900-BBK: Battery Backup – back up power in case of power outage, includes batteries
  • 900-FA: Fire Alarm – relay for interface with fire alarm panel  – wires to main board
  • 900-2Q: 2 Relay QEL control Board – to run 2 Von Duprin QEL devices
  • 900-2RS: 2 Relay EL Control Board – to run up to 2 Von Duprin EL devices
  • 900-4R: 4 Relay Output Board – four relay outputs to operate 4 electric locking devices, not QEL or EL
  • 900-4RL: 4 Relay Logic Board – for man trap or security interlock systems
  • 900-8F: Fused 8 Zone Distribution Board – 8 outputs, fused for circuit protection
  • 900-8P: PTC 8 Zone Distribution Board – 8 outputs, circuit breaker protected

PS906 can accommodate up to 3 option boards, fire alarm interface (with option board) and battery back up.

For use with electric locks and with up to 6 Von Duprin Quiet Electric Latch retraction (QEL) exit devices, but NOT with Von Duprin electric latch retraction (EL) exit devices.

PS914 – 4 Amp output at 12 or 24VDC, field selectable

Compatible with these option boards:

  • 900-BBK: Battery Backup – back up power in case of power outage, includes batteries
  • 900-FA: Fire Alarm – relay for interface with fire alarm panel  – wires to main board
  • 900-2Q: 2 Relay QEL control Board – to run 2 Von Duprin QEL devices
  • 900-2RS: 2 Relay EL control Board – to run up to 2 Von Duprin EL devices
  • 900-4R: 4 Relay Output Board – four relay outputs to operate 4 electric locking devices, not QEL or EL
  • 900-4RL: 4 Relay Logic Board – for man trap or security interlock systems
  • 900-8F: Fused 8 Zone Distribution Board – 8 outputs, fused for circuit protection
  • 900-8P: PTC 8 Zone Distribution Board – 8 outputs, circuit breaker protected

PS914 can accommodate 2 of the above option boards, plus fire alarm interface (on one of the boards) and battery back up.

Capable of powering:

  • Up to 4 Electric Latch retraction (EL) exit devices with 900-4RL board
  • Up to 2 EL devices with 900-2RS board
  • Up to 4 Quiet Electric Latch retraction (QEL) exit devices
  • Up to 4 Chexit (CX) delayed egress exit devices off the main board (use 900-8FA combination board if Fire Alarm relay is required)
  • Electric locks or strikes

 

Ordering Tips:

PS-914 is a 4 Amp power supply that is double the capacity of the old PS873, however, from my conversation with IR tech support, their feeling is that it is prudent to power no more than 4 EL devices per PS-914.  Theoretically the power supply could support as many as 8 EL devices however this presents the challenge of timing the relays so that no two can change states at the same time.  If two EL devices are powered up simultaneously the PS-914 could be damaged.

None of the PS900 series power supplies are a drop-in replacement for their predecessors, and the old and new option boards are not cross-compatible with the old and new power supplies.  Therefore, replacing old power supplies with new can present a rewiring challenge.

Ordering back-up batteries can be a little tricky, since they have very similar part numbers for the batteries, the charging circuit board, and a set that includes the board and the batteries.

  • 900-BAT – Pair of batteries only
  • 900-BB – Battery back up board only
  • 900-BBK – Power battery back up kit, board and batteries

 

 

Glass Door Electric Locking Solutions

Installing an electric locking system on an existing, currently unsecured all-glass or Herculite door can be a challenge for the security professional, but there are solutions.  Here are a few:

Electromagnetic Locks

Securitron Glass Door Solution

The Securitron solution to the glass door locking problem is… glue.   When I sell this solution, I usually use:

  • M62G (1200 lb. holding force electromagnetic lock with conduit fitting)
  • AKG (adhesive kit for glass doors)
  • GDB (glass door bracket for armature)

For all glass doors with all glass headers, I also use the HEB-G header extension bracket.  This can also be glued in place using the Securitron AKG.  Since the AKG includes enough glue to do 10 glass-door mag installs, there is more than enough to do one all-glass door and one all-glass header.

Everybody Else’s Mag-Lock-for-Glass-Door Solution

As far as I know, no one besides Securitron really deals with the situation of an all glass header.  For all-glass doors, all the other companies that make electromagnetic locks use variations of the HDB, or Herculite Door Bracket.  This bracket is a U-channel that slides down over the top of the door.  It’s a clip-on system:

Illustration from Rutherford Controls web site

The Herculite door bracket concept seems to work well except in cases were there is a reduced gap between the top of the door and the header.  In that case the U-channel idea is out because the HDB bracket will keep the door from closing.  Then it’s the Securitron and the glue or something else altogether.

RCI Cushion-Lok

A pricey but classy and easy to install alternative to the electromagnetic solution is the Rutherford Controls Cushion-Lok.  The Cushion-Lok is a specially constructed, fail safe electric strike and passive latch that gently locks the door upon closure.   Shown below is the RCI 3360 which is pre-installed on patch fittings that slide onto the glass of the door and “frame” when the entire doorway – door, lintels and header – is made of glass.

Not shown is another version for use with a wood or metal frame and Herculite door.

It is worthwhile to note that the reason security professionals are faced with installing electric locks on existing all-glass doors is because of a lack of planning on the part of the architect or project manager.  It is much easier for a glass door manufacturer to pre-install a locking system than it is for a security professional to install it after the fact.

Locking People In

I often get a request to help create a system that locks people in.  People want to lock children inside a daycare center, students inside a “Time-Out” room, babies inside a nursery in a maternity hospital or patients inside, for example, an Alzheimer’s disease in-patient facility for their own good.

“Well, what if there’s a fire?” I ask.

That’s really the issue.  If we are keeping them in, how are they supposed to get out in the event of a fire?  Yet, except when there is a fire or other emergency that renders the building unsafe, it is in their best interest if they are kept inside.

Often, people simply want to lock people in with an electromagnetic lock or other device.  Since this is certainly a violation of life safety code, any injury that may result would be uninsurable and could invite litigation.

I discuss delayed egress systems in depth in another article (click here to read).     A delayed egress system is really the right way to do this, since it is actually covered in the NFPA 101A Special Locking Arrangements section of the fire safety code, but it is fairly inconvenient to use.  To get out without setting off an alarm users must use some kind of bypass request to exit switch like a keypad, card reader or key switch – much less convenient than, say, simply pushing a door open via the push pad on an exit device.

The gist of a delayed egress system is that, after a short ‘nuisance’ delay, the lock sounds an alarm for fifteen seconds and then lets the person out.  That means that authorities on the secured premises have fifteen seconds to get to the exit and prevent unauthorized egress.

Where unauthorized egress is not a life threatening prospect, therefore, a delayed egress system is perfectly adequate.  However, when a person’s life may depend on being kept inside their care facility, a more complex solution maybe required.

A great solution for Alzheimer’s or other dementia care facilities is the WanderGuard system by Stanley.  This system is designed for Alzheimer’s and other health care facilities where unscheduled patient departure is an issue, and covers other needs with fall monitoring and patient call capabilities.  Patients are fitted with bracelets that serve as tracking and communication devices.  As one might expect, such a system is not inexpensive and a bit on the overkill side for use in a day care center or maternity facility.  To physically keep people inside the facility, the WanderGuard system is designed to interface with delayed egress locks.

I think that the WanderGuard system would be a good choice for use in maternity ward nurseries as well.

The situation is more challenging when you have a day care center or a “Time-Out” room.

I had heard that Schlage was coming out with a mechanical time out lock, but a search as of today renders only the same Time-Out Room solution:  An electromagnetic lock with a momentary pushbutton.  The troublesome child is forced into a room, the door is shut, and then the teacher or other disciplinarian must physically press the momentary contact pushbutton to keep the magnetic locked locked.  As soon as the teacher lets go, the child is free.

As long as the button is momentary, I have no problem with this idea.  Should there be a fire or other life safety emergency, even if the teacher panics and runs away, leaving the child in the Time Out Room, the child will still be able to leave the room and exit the building.

The right way to prevent the kids in a daycare center from running out of the building and into the street without permission is with a delayed egress system.  True, it may be cumbersome to punch in a code on a keypad or present a proximity card for authorized egress, but delayed egress systems can be easily deactivated for periods of time, say, for drop off and pick up.  A delayed egress system is more expensive than, for example, an electromagnetic lock connected to the fire alarm system for safety.  But if you run the scenario of a fire in your mind, the fire alarm interface to the electromagnet malfunctions, panicked children and day care providers flinging themselves against an illegally locked door, too crazed with fear to think – suddenly a delayed egress system makes a lot more sense.

There is really only one place you can really lock someone in, and that’s in a jail or prison.  Otherwise there must be some provision to let them out – for safety’s sake.

 

Understanding Door Security Monitor Switches

A number of different kinds of switches are available to help you keep track of whether or not your door is shut and / or locked.  Here are some of them:

Door Status Monitor Switch

A door status monitor switch changes states when the door is opened or closed.  Typically this is accomplished by using a magnetic reed switch, either surface mounted or concealed in the edge of the door and door frame like the one shown at right.

How a Magnetic Reed Switch Works

The magnetic reed switch is typically installed on the door frame and the magnet that activates the switch is typically installed on the door.   Inside the magnetic reed switch, a thin piece of steel – a steel ‘reed’, if you will – is held in position by the attraction of the magnet when the door is closed.  When the door is opened, the magnet is taken away from the switch and the spring tension of the “reed” causes it to spring back against the other contact, changing the state of the switch.

Most magnetic reed switches are normally closed – “closed loop” – but are also available normally open (“open loop”) SPDT (single pole double throw, or “form C”) or DPDT (double pole double throw).

The Purpose of the Door Status Monitor Switch

The door status monitor switch is used to notify remote devices that a door is open or closed.  Typically these remote devices are burglar alarm panels or access control system controllers.   It does not tell you if the door is locked, just if it is closed.

Request to Exit Switch

The request to exit switch, also known as a REX switch, is so named because it is usually connected to the request to exit contacts on an alarm panel or access control board.  It is used to notify an external device that someone is exiting through, or wants to exit through, a door.  REX switches come in a wide variety of configurations, from push button palm switches engraved “push to exit” to switches concealed inside exit devices.  A motion exit sensor is also a form of request to exit switch.

Request to exit switches are available with a wide variety of contact configurations and with or without electronic or pneumatic time delay.   If the switch is being used as a means of egress for pedestrian traffic, it will need to comply with life safety code.  Life safety code varies from locality to locality as governed by your local AHJ – Authority Having Jurisdiction – that is, your local building inspector or fire marshal.

Latch Bolt Monitor Switch / Strike Monitor Switch

I write about Latch Bolt Monitor (LBM) switches and Strike Monitor Switches because they somewhat overlap.  Both are designed to monitor the position of the latch bolt.

Some LBM switches are inside locks and others are in electric strikes.  From inside the lock, they monitor whether the latch is extended or depressed.  When located in an electric strike, they monitor whether or not there is a latch bolt present in the keeper.

Pictured at right is Securitron’s line of inexpensive strike monitor switches as examples of strike monitor switches.  Several companies offer like products.  Strike monitor switches are an easy way to monitor if there is a latchbolt (or some other object) present in the keeper.   Several companies, such as Von Duprin, offer heavier duty monitor strikes.  Monitor strikes are sold as a finished unit that includes as strike and a switch whereas strike monitor switches are aftermarket add-on units.

Magnetic Bond Sensor / Bond Sensor

Magnetic bond sensor and bond sensor options refer to electromagnetic lock applications.  Many manufacturers offer Bond Sensor or Magnetic Bond Sensor as an option.  What this does is allow an electromagnetic lock to notify some external device that its holding force is below spec.  Authorities are alerted and the situation is addressed.

Maximizing Effectiveness

To maximize effectiveness of door monitor switches, it is best to use both a door status monitor and some kind of lock status monitor as well, and this is why:  because monitor switches can be fooled.  A door status switch will tell you if the door is open or closed – unless it has been altered to tell you the door is closed when it is not.  Also, a door may be closed, but not locked.  If you have a latch bolt monitor or magnetic bond sensor in place as well as a door status switch, you will know if the door is closed but not locked.

This is the center of this knowledge:  to know that the door is shut AND locked.

 

 

 

What’s Hot in Door Hardware

A couple of new innovative products have recently caught my attention.  Here they are:

Security Door Controls (SDC) Model LR100VDK:

Field Installed Electric Latch Retraction Retrofit Kit for Von Duprin Exit Devices

 

 

 

 

 

 

 

 

This product is available now.

http://www.sdcsecurity.com/whatsnew2.aspx#lr100

The mere 450mA inrush powering Security Door Controls’ new electric latch retraction retrofit kit is attractive enough.  Its compatibility with all Von Duprin touch bar style devices may make it just about irresistible.   Optional request to exit switch kits are available.  The unit is usable for access control and electric dogging applications.

The small inrush is huge.  (I always wanted to say that.)  High inrush electric latch retraction requires special, expensive power supplies.  Not so with the LR100VDK.  Your average regulated and filtered 1-amp 24vdc power supply will do nicely, thank you.

Another great aspect of this kit is that it is compatible with the Von Duprin 22 series exit device. So now, for relatively short money you can give a customer electric latch retraction in a decent quality exit device.

HES Model 8500 Electric Strike for Mortise Locks


http://www.hesinnovations.com/en/site/hesinnovations/Products-startpage/?groupId=141798&productId=764670

This product is due to become available by the end of August, 2011, but we’ll see.

Hanchett Entry Systems’ new lipless electric strike solution for mortise locks.

Installing an electric strike to release a mortise lock will be much easier with the HES 8500 since no cutting of the face of the frame is necessary.  Below is an illustration showing the difference between the HES 1006 standard electric strike for mortise lock and the new HES 8500.

HES 1006 prep for hollow metal

HES 8500 door prep for hollow metal - look ma, no lip!

 

 

 

 

 

 

 

 

 

 

 

 

This is not a new idea, but installers seem excited about the prospect of having an alternative to the Securitron UnLatch, which has been around for quite some time.  The Unlatch model that the HES 8500 will compete with will be the Securitron MUNL.

Of course, the advantage the MUNL currently enjoys is that, unlike the 8500, one can actually buy an MUNL.  Comparatively, the Securitron requires a door frame depth of about 1-7/8 inches whereas the the 8500 will require about 1-3/8 inches.  The 8500 will draw 240mA at 12 volts DC and 120mA at 24 volts DC and draws no inrush current.  The MUNL has an inrush of 2 amps at 24vdc or 4 amps at 12vdc and an operating current of 600mA at 12vdc or 300mA at 24vdc.  One important result of the lower current consumption of the 8500 will be that instead of the 4 amp 12vdc or 8 amp 24vdc power supply necessary for each MUNL, one 8 amp 24vdc power supply will theoretically power as many as perhaps 60 of the new HES 8500.  Of course then, factors like wire run will come into play, but still.

Another positive attribute will be that the 8500 will be field selectable for fail safe or fail secure whereas the MUNL requires an additional module to make it fail safe.

All in all, the 8500 seems that it will be a better choice all around.  We’ll just have to wait and see how it performs in the field after it becomes available at the end of August 2011.


Tags